Item
|
Smart UPS
|
VA Rating - UPS Systems
|
750.0 VA
|
UPS Type
|
Line Interactive
|
Power Rating
|
750VA
|
Watts - UPS Systems
|
450.0 W
|
Input Voltage - UPS Systems
|
120V AC
|
Mounting
|
Rack
|
Output Voltage - UPS Systems
|
120V AC
|
Wattage
|
600 W
|
Input Voltage
|
120V AC
|
Output Voltage
|
110/115/120V
|
Backup Time (Half/Full Load)
|
13.2 min/4.9 min
|
Outlet Type - UPS Systems
|
UPS/Surge
|
Outlet Type
|
UPS/Surge
|
Medical Grade
|
No
|
Number of Outlets
|
6
|
NEMA Receptacle Configuration
|
5-15R
|
Transfer Time
|
2 to 4 msec
|
Watts
|
450W
|
Special Features
|
Advanced AVR Corrects Brownouts and Overvoltages, Pure Sine Wave Output
|
Input Current
|
7 A
|
Display Type
|
LED
|
Fax/Modem Line Protection
|
No
|
Includes
|
Cables for USB and DB9 Monitoring and EPO Switching, Mounting Hardware, PowerAlert Unattended Shutdown and UPS/Power Monitoring Software
|
Automatic Volts Regulation
|
Yes
|
NEMA Plug Configuration
|
5-15p
|
Hz
|
60 Hz
|
Ports
|
DB9 Serial, EPO, SNMP/Web Slot, USB
|
Standards
|
Meets FCC Part 15 Category A (EMI), Tested to CSA (Canada), Tested to NOM (Mexico), UL1778 (USA)
|
Mounting - UPS Systems
|
Rack
|
Phase
|
1
|
Footnotes
|
3,4,10,12
|
Input Connection
|
10 ft Cord with NEMA 5-15P Plug
|
UPS Input Connection Type
|
5-15P
|
Output Voltage Regulation (Battery Mode)
|
+/- 5%
|
Frequency Compatibility
|
60 Hz
|
Included Mounting Accessory Description
|
Included mounting brackets provide front-rail installation in 2 or 4 post racks; For additional stability in 4 post racks, consider optional 4 post mounting accessories 4POSTRAILKIT1U & 4POSTRAILKITWM
|
LED Indicators
|
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
|
Output Voltage Regulation (Line Mode)
|
-21%, +8%
|
High Voltage Transfer to Battery Power (Setpoint)
|
147
|
Grounding Lug
|
Back panel grounding lug
|
Output Watt Capacity (Watts)
|
600
|
Primary Form Factor
|
Rackmount
|
Internal UPS Replacement Battery Cartridge
|
RBC64-1U
|
Audible Alarm
|
Audible alarm indicates power-failure, overload and low-battery conditions
|
Installation Form Factors Supported with Included Accessories
|
2 post 19 inch rackmount; 4 post 19 inch rackmount
|
Operating Temperature Range
|
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
|
Nominal Voltage Details
|
120v nominal output in battery mode
|
Alarm Cancel Operation
|
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate low-battery status
|
Input Phase
|
Single-Phase
|
Overvoltage Correction
|
Input voltages between 128 and 147 are reduced by 12%
|
Output AC Waveform (Battery Mode)
|
Pure Sine wave
|
EMI / RFI AC Noise Suppression
|
Yes
|
Network Monitoring Port Description
|
Supports detailed monitoring of UPS and site power conditions
|
UPS AC Suppression Response Time
|
Instantaneous
|
Rated input current (Maximum Load)
|
7A
|
Nominal Output Voltage(s) Supported
|
110V; 115V; 120V
|
Communications Cable
|
USB and DB9 cabling included
|
Voltage Regulation Description
|
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 147
|
Nominal Input Voltage(s) Supported
|
120V AC
|
High Availability UPS Features
|
Hot swappable batteries
|
Output Receptacles
|
(6) 5-15R
|
AC Mode BTU / Hr. (Full Load)
|
38
|
PowerAlert Software
|
For local monitoring via the UPSâ„¢s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert
|
Communications Interface
|
USB; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
|
UPS AC Suppression Joule Rating
|
450
|
Recommended Electrical Service
|
15A 120V
|
Output AC Waveform (AC Mode)
|
Sine wave
|
AC Mode Efficiency Rating (100% Load)
|
0.98
|
Battery Recharge Rate (Included Batteries)
|
Less than 4 hours from 10% to 90% (typical, full load discharge)
|
Battery Mode BTU / Hr. (Full Load)
|
545
|
Cold Start (Startup in Battery Mode During a Power Failure)
|
Cold-start operation supported
|
Input Circuit Breakers
|
15A
|
Storage Temperature Range
|
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
|
WatchDog Compatibility
|
Supports Watchdog application, OS and hard-reboot restart options for remote applications
|
Relative Humidity
|
0 to 95%, non-condensing
|
Battery Replacement Description
|
Hot-swappable, user replaceable batteries
|
DC System Voltage (VDC)
|
24
|
Output Volt Amp Capacity (VA)
|
750
|
Switches
|
2 Switches control off/on power status and alarm-cancel/self-test operation
|
Power Factor
|
0.8
|
Audible Noise
|
45 dBA maximum, front side 1m
|
Undervoltage Correction
|
Input voltages between 83 and 107 are boosted by 14%
|
Expandable Runtime
|
No
|
Full Load Runtime (min.)
|
4.9 min. (600w)
|
Half Load Runtime (min.)
|
13.2 min. (300w)
|
Individually Controllable Load Banks
|
Yes
|
UPS Housing Material
|
Steel
|
Low Voltage Transfer to Battery Power (Setpoint)
|
83
|
Installation Form Factors Supported with Optional Accessories
|
4 post rackmount full-depth ( 4POSTRAILKIT1U ); 4 post rackmount short-depth ( 4POSTRAILKITWM )
|
Load Management Receptacles
|
Two switchable single-outlet 5-15R load banks
|
Battery Access
|
Front panel battery access door
|
Cooling Method
|
Fan
|
UPS Certifications
|
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)
|
Network Management Cards
|
SNMPWEBCARD ; TLNETCARD ; WEBCARDLX
|
Product Name
|
SmartPro 750RM1U UPS
|
Hot Swappable
|
Yes
|
Receptacle Detail
|
6 x NEMA 5-15R
|
TAA Compliant
|
Yes
|
Status Indicators
|
5 front panel LEDs - Green POWER LED, 3 color BATTERY CHARGE LED, 3 color OUTPUT LOAD LEVEL LED, red BATTERY WARNING LED.
|
Product Type
|
Line-interactive UPS
|
Certifications & Standards
|
UL1778 (USA), cUL (Canada), FCC Class A (emissions), NOM (Mexico), Conforms to IEEE 587 / ANSI C62.41 specifications
|
Total Number of Expansion Slots
|
1
|
Plug/Connector Type
|
NEMA 5-15P
|
USB
|
Yes
|
Battery Chemistry
|
Lead Acid
|
Load Capacity
|
750 VA/600 W
|
Backup/Run Time (Half Load)
|
13.20 Minute
|
Product Line
|
SmartPro
|
Package Contents
|
SMART750RM1U UPS System, Mounting hardware, Cabling for USB & DB9 monitoring and EPO switching, PowerAlert unattended shutdown and UPS/Power monitoring software, Warranty information and instruction manual
|
Typical Battery Recharge Time
|
4 Hour
|
Network Management
|
SNMP Manageable
|
Backup/Run Time (Full Load)
|
4.90 Minute
|
Alarm
|
Overload, On Battery, Low Battery
|
Maximum Operating Temperature
|
104°F (40°C)
|
Battery Life
|
6 Year
|
Emergency Power OFF
|
Yes
|
Waveform Type
|
Sine Wave
|